Production Capacity: 22000PCS/Year Electrical Breaker
Transport Package: Wooden Case Packing (900*900*1000mm)
Payment Terms: L/C, T/T, Western Union, Paypal

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: VMD
  • Operation: Manual and Electric Type Electrical Breaker
  • Arc-extinguishing Medium: Vacuum
  • Structure: Vcb Electrical Breaker
  • Type: Circuit Breaker
  • Certification: ISO9001-2000, CCC, Ohsas 180001
  • Rated Current: 1600A Electrical Breaker
  • Lighting Impulse Withstand Voltage: 75kv Electrical Breaker
  • Rated Short-Time Withstand Current: 20\25\31.5\40 Ka Electrical Breaker
  • Specification: OHSAS/ OHSMS 18001, ISO9001
  • HS Code: 8535210000
  • Breaking Capacity: High and Medium Voltage Electrical Circuit Breaker
  • Speed: Normal Type Circuit Breaker
  • Installation: Fixed and Handcart Type Electrical Breaker
  • Poles Number: 3
  • Function: Overcurrent Protection
  • Rated Voltage: 12kv Electrical Breaker
  • 1 Min Power Frequency Withstand Voltage: 42kv Electrical Breaker
  • Rated Frequeny: 50/60Hz Electrical Breaker
  • Trademark: Mingde Electrical breaker
  • Origin: Cixi, Ningbo Electrical Breaker
Product Description

Hot Sale 12kv-1600A 3 Phase High-voltage Vmd Vacuum Circuit Breaker


Overview

 

1. The complete specification of VMD series vacuum circuit breaker can meet customers' different needs.

 

2.  VMD adopts the latest embedded poles and low-resistance vacuum interrupter.With main conductive circuit sealed in epoxy resin, the insulation performance will be more stable.

 

3. VMD employs an accurate gear driving system, instead of the traditional chain wheel driving system. 

 

4. VMD series circuit breaker passed Type Test Report according to GB and IEC standards.

 

5. VMD series circuit breaker has exported to 26 countries and regions in the world.


Technical Parameters

NOItem UnitTechnical Data
1Rated voltageKV12
21 min power frequency withstand voltage42
Lighting impulse withstand voltage(peak value)75
3Rated FrequencyHz50
4Rated currentA1600
5Rated short time withstand currentKA20,25,31.5,40
6Rated withstand current(peak)50,63,80,100
7Rated short-circuit opening current20,25,31.5
8 Rated short-circuit closing current 50,63,80
9Rated duration of short-circuit S4
10Contact's clearance 3.5±0.5
11Contact's travel 9±1/11±1
12Average opening speedm/s1.1±0.2
13Average closing speed m/s0.6±0.2
14Opening timems35-60
15Closing timems20-45
16Mechanical life times30000
17Rated operating order O-0.3S-CO-180S-CO

 
External Dimensiomns


Hot Sale 12kv-1600A 3 Phase High-Voltage Vmd Vacuum Circuit Breaker


VMD2-7.2,12,17.5-pole center distance 150mm

No.Rated Voltage(kV)Rated current(A)Short-circuit breaking current(kA)h1(mm)h2(mm)h(mm)A(mm)B(mm)
17.2,12,17.5630-125020-31.5260205622438609
27.2,12,17.5630-125020-31.5280275637432598
 

 

Hot Sale 12kv-1600A 3 Phase High-Voltage Vmd Vacuum Circuit Breaker


VMD2-7.2, 12, 17.5-pole center distance 210mm

 

No.Rated Voltage(kV)Rated current(A)Short-circuit breaking current(kA)h1(mm)h2(mm)h(mm)A(mm)B(mm)
17.2,12,17.5630-125020-31.5260205622438609
27.2,12,17.5630-160020-31.5280275637432598
37.2,121250-160040295310697432598
47.2,12200031.5-40295310697432598
   


Hot Sale 12kv-1600A 3 Phase High-Voltage Vmd Vacuum Circuit Breaker


VMD2-7.2, 12, 17.5-pole center distance 275mm

 

No.Rated Voltage(kV)Rated current(A)Short-circuit breaking current(kA)h1(mm)h2(mm)h(mm)A(mm)B(mm)
17.2,12,17.5630-125020-31.5280275637432598
27.2,121250-160040295310697432598
37.2,121600-250025-40295310697432586
47.2,123150-400031.5-40295310697432586
57.2,123150-400031.5-40295310733432586
 
Packaging, Transportation and Storage Precautions

 

(1) Circuit breaker should be in the state of opening and energy storage spring in a state without energy storage when packing. It should be in the state of opening and energy storage spring in a state without energy storage when packing. And it should be fixed on the bottom of the wooden case, should have waterproof measures and complete package labels.
(2) Circuit breakers can't invert and avoid strong vibration, rain, surface damage, and components lost when transportation.
(3) When loading the circuit breaker, we suggest the following tools: crane, forklift and driving. When lifting the circuit breaker, we should not hook on the body or pole of the circuit breaker, but on the lifting hole which has the lifting mark.
(4) When circuit breaker has a long-term storage, it should be in a state of opening and energy storage spring in a state without energy storage and placed in dry ventilated indoor preventing from moisture, vibration control and harmful gas erosion, and regularly checked whether environment meets the requirements.
(5)When first use products after long-term storage, it need to have a power frequency withstand voltage insulation testing.
 
Send your message to this supplier
Avatar
Mrs. Sophie
Manager
*From:
To: Mrs. Sophie
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

Find Similar Products By Category